Power Testing Equipment

Short Description:

Explore load banks for data center commissioning and power system testing. Choose from system-level, rack-mounted and liquid-cooled configurations for generator and UPS load tests, rack-level load simulation and liquid cooling loop testing.


Product Detail

Product Tags

Product Overview

A load bank applies a controlled load so commissioning teams can evaluate how equipment responds under specified test conditions. For data center projects, the choice starts with where the load will be applied and what the test needs to verify.

● System-level power testing applies load at the generator, UPS or distribution test point.

● Rack-level load simulation places test loads at cabinet positions to represent planned IT power demand.

● Liquid cooling testing applies a thermal load to the coolant loop so the team can evaluate the cooling system under defined conditions.

Specify the test point, voltage, load profile and control requirements before selecting equipment. For liquid cooling tests, also define the heat load and coolant connection conditions.

Product Series

Power System Load Banks
Power system load banks are used for generator, UPS and distribution equipment testing at designated connection points. The range includes portable units, manual-control and operator-console configurations, and medium-voltage load banks with remote computer control.
Representative models include the MT-100KW portable load bank and the MT-R600KW, listed at 600 kW, 400 V AC and a power factor of 1.0, with local manual and operator-console control. The MT-MV-3000KW is listed at 3 MW and 10.5 kV with remote laptop control. Select the configuration according to the required load, test voltage, power factor and control method.

Data Center Rack Load Banks

Rack-mounted load banks place test loads at the cabinet positions where IT equipment will operate. Units can be distributed across a row of cabinets to apply the planned load to the rack feeds and upstream power distribution equipment.
Model or Configuration Listed Load Listed Supply
MT-AC/DC4KW 4 kW AC/DC configuration
MT-AC/DC12KW 12 kW AC/DC configuration
MT-5KW220V 5 kW 220 V AC
230 V AC Rack-Mounted Load Bank Group Confirm for the selected unit 230 V AC
For selection, specify the input voltage, target load per rack, number of rack positions and available mounting space.

Liquid Cooling Test Load Banks

Liquid-cooled load banks apply a controlled heat load during cooling loop commissioning. Rack-mounted configurations allow the test team to place the load at specified cabinet positions and assess the coolant loop under the intended test conditions.
The range includes 15 kW and 30 kW configurations and a 30 kW continuously adjustable rack-mounted series. Specify the target heat load per rack, total loop heat load, coolant inlet temperature, flow rate and connection requirements when requesting a configuration.

Technical Specifications

Series rows show the published range for a product family. Model rows show the listed specifications for an individual unit. Confirm the required voltage and load combination when selecting a configuration.
Model / Series Rated Load Rated Voltage Power Factor Control Mode Dimensions Weight Operating Temperature
1,000–2,000 kW Power System Series 1,000–2,000 kW 400–690 V AC 1 — — — —
MT-100KW Portable Load Bank 100 kW — — — — — —
MT 400 kW Manual Load Bank Series 400 kW 400 V AC 1 Manual control — — —
MT 500–1,000 kW Operator-Console Series 500–1,000 kW 400 V AC 1 Operator-console configuration — — —
MT-R600KW 600 kW 400 V AC 1 Local manual and operator-console control 1,500 × 1,500 × 2,000 mm 2 t −10 to +55 °C
MT-MV-3000KW 3 MW 10.5 kV — Remote laptop control 6,058 × 2,438 × 2,591* 7 t −35 to +55 °C
MT-MV-2500KW-20KV 2.5 MW 20 kV — Remote laptop control 9,000 × 2,438 × 2,896* 12 t −10 to +55 °C
MT-MV3150KVA-10.5KV 3,150 kVA / 2,500 kW† 10.5 kV 0.8† Remote laptop control 9,000 × 2,438 × 2,896* 12 t −10 to +55 °C

Testing Applications

The values below describe reference test configurations. Select the load bank or combination of units for the voltage, current or power required at the actual test point.
  • Generator Load Testing:
Apply a defined load to evaluate generator performance during commissioning or acceptance testing. The test plan determines whether the configuration requires resistive, resistive-capacitive or resistive-inductive loading.
Reference conditions — 1–20 MW, with listed AC test voltages of 440 V, 690 V, 3.3 kV, 4.16 kV, 6.6 kV, 10.5 kV and 13.8 kV. The application data also lists a power factor range of 0.4–0.8. Confirm the applicable load type and target power factor for the test.
  • UPS Load Testing:
Apply a defined output load to evaluate how the uninterruptible power supply responds at the required load levels. Select the load bank around the UPS output voltage, target load and test sequence.
Reference conditions — 10 kW–4 MW. Listed test configurations include 220 V AC, 400 V AC and 10.5 kV AC.
  • Battery Discharge Testing
Apply a controlled DC load to evaluate battery bank performance during discharge. Define the DC voltage, discharge current and test duration when selecting the discharge equipment.
Reference conditions — 10–10,000 A, with listed configurations at 48, 240, 270, 480, 600 and 720 V DC.
  • Power Distribution System Testing
For distribution tests, define which part of the system is under test and the load to be applied at that point. Rack-mounted units can be distributed across cabinets for row-level tests. Switchgear, transformers and busway require configurations selected around the project’s test voltage, current or power.
Application Test Purpose Reference Conditions
Row Power Distribution Cabinets Apply the planned load to the cabinet and downstream rack feeds. 220 V AC reference configuration covering 1,000 racks and 5,000 kW of test load.
Switchgear Evaluate the switchgear under the current specified for the test. 250–6,300 A at listed voltages of 440 V, 690 V, 6.6 kV and 10.5 kV AC.
Transformers Apply the load specified for the transformer test. 1,000–10,000 kW, with listed configurations at 400 V AC and 10.5 kV AC.
Busway Apply the target current to the busway section under test. 100–10,000 A at listed voltages of 400 V, 690 V, 6.6 kV and 10.5 kV AC.

Request a Quote

Tell us what you need to test, the target load at each test point and your commissioning schedule. For rack-level or liquid cooling tests, include the number of rack positions and the required load per rack. This information helps us identify a configuration for your project.